Waterline Controls
Waterline - Model WLC-4000 -Simplex Fill Control & High Alarm
The WLC-4000 combines precision fill control with a high level alarm. Complete Kit Includes: NEMA 4X Enclosure with Lockable SS Latch and Power Relays. Sensor with 50 ft. Cable*. Side Wall Mounting Assembly.
Most popular related searches
- Model: WLC-4000
- Functions: Fill / High Alarm
- Input Power: 110VAC / 110VAC Standard (30VDC, 24VAC, 240VAC available)
PANEL SPECIFICATIONS
- DPDT Power Relays: 2
- DPDT Power Relay Rating: 120VAC @ 40A (N.O.) / 120VAC @ 30A (N.C.)
- SPST Dry Contacts for Remote Signaling (BMS, BAS, or Other): 3
- SPST Dry Contact Rating: 30VDC @ .5A
- SPST Dry Contact Functions: (1) Power-loss, (2) Control Functions
- LED Indicators: 3
- Press to Test: Yes
- Audible Alarm: Available upon request
- Alarm Beacon: Available upon request
- Temperature Alarm: Available upon request
ENCLOSURE SPECIFICATIONS
- Rating: NEMA 4X (Indoor/Outdoor)
- Material: Polycarbonate
- Size: L: 10-1/2 ” W: 9-1/2″ H: 5″
- Panel Door: Hinged, Non-Transparent (Clear available upon request)
- Latch: Stainless Steel (Lockable latch available upon request)
- Panel Faceplates: Aluminum
LEVEL PROBE SPECIFICATIONS
- Plug Style: 3″ PVC Slip-Plug
- Sensor Head Material: PVC
- Sensor Head Size: 3″ diameter (round)
- Probe Material: PVC Heat-Shrink, Stainless Steel
- Probe Length:
- High Alarm (Green) 10-3/8″
- Fill Stop (Red) 14″
- Fill Start (White) 17″
- Reference (Black) 17″
- Probes Extendable? Yes, and up to any length (18″/45.5″ Extension Kits available)
- Jefferson Valve (3/4″-2″)
- OCV Valve (2″-12″)
- Superior Valve (3/4″- 2″)
- Extension Rod Kits
- Audible Alarm
- Top of Panel Beacon
- H.O.A. Switches
- Remote Indication Panels
- Light Towers
- 5-Year Limited Warranty
- Life of Product Technical Support