Waterline Controls

WaterlineModel WLC-4000 -Simplex Fill Control & High Alarm

SHARE

The WLC-4000 combines precision fill control with a high level alarm. Complete Kit Includes: NEMA 4X Enclosure with Lockable SS Latch and Power Relays. Sensor with 50 ft. Cable*. Side Wall Mounting Assembly.

Most popular related searches
  • Model: WLC-4000
  • Functions: Fill / High Alarm
  • Input Power: 110VAC / 110VAC Standard (30VDC, 24VAC, 240VAC available)

PANEL SPECIFICATIONS

  • DPDT Power Relays: 2
  • DPDT Power Relay Rating: 120VAC @ 40A (N.O.) / 120VAC @ 30A (N.C.)
  • SPST Dry Contacts for Remote Signaling (BMS, BAS, or Other): 3
  • SPST Dry Contact Rating: 30VDC @ .5A
  • SPST Dry Contact Functions: (1) Power-loss, (2) Control Functions
  • LED Indicators: 3
  • Press to Test: Yes
  • Audible Alarm: Available upon request
  • Alarm Beacon: Available upon request
  • Temperature Alarm: Available upon request

ENCLOSURE SPECIFICATIONS

  • Rating: NEMA 4X (Indoor/Outdoor)
  • Material: Polycarbonate
  • Size: L: 10-1/2 ” W: 9-1/2″ H: 5″
  • Panel Door: Hinged, Non-Transparent (Clear available upon request)
  • Latch: Stainless Steel (Lockable latch available upon request)
  • Panel Faceplates: Aluminum

LEVEL PROBE SPECIFICATIONS

  • Plug Style: 3″ PVC Slip-Plug
  • Sensor Head Material: PVC
  • Sensor Head Size: 3″ diameter (round)
  • Probe Material: PVC Heat-Shrink, Stainless Steel
  • Probe Length:
    • High Alarm (Green) 10-3/8″
    • Fill Stop (Red) 14″
    • Fill Start (White) 17″
    • Reference (Black) 17″
  • Probes Extendable? Yes, and up to any length (18″/45.5″ Extension Kits available)

  • Jefferson Valve (3/4″-2″)
  • OCV Valve (2″-12″)
  • Superior Valve (3/4″- 2″)
  • Extension Rod Kits
  • Audible Alarm
  • Top of Panel Beacon
  • H.O.A. Switches
  • Remote Indication Panels
  • Light Towers

  • 5-Year Limited Warranty
  • Life of Product Technical Support