- Home
- Companies
- Kurz Instruments, Inc.
- Products
- Kurz - Model Series 155 - Mass Flow ...
Kurz - Model Series 155 -Mass Flow Computer/Transmitter
The various models operate one or more Kurz Mass Flow Elements including Series 452, 502, 522-UHP, K-BAR 16, K-BAR 24, K-BAR 2000, the Series IK-4200 Isokinetic Sampling Probes and the Series 730 Mass Flow Control Valves .
The Series 155 may also be used with the new MFT Series of Mass Flow Transmitters (454FT, 504FT, 534FT, K-BAR 2000) as a convenient power supply, display and Mass Flow Computer for remote sensor electronics applications.
The Series 155 integrates the functions of flow and temperature measurement, flow totalization, alarms, data acquisition, input/output calibration and closed loop flow control. Models are available to operate up to 22 separate two-wire, loop-powered Kurz mass flow or temperature elements. The smaller Model 155`s have two analog 4-20 mA outputs; the larger models support up to eight 4-20 mA outputs. All Models include a convenient 2 line, 16 character LCD display and 20 button keypad to display the measurements, input all calibration and set-up data, and perform input/output calibration of each input and each analog output.
- Easy-to-use menu for display and set-up with Help screens
- Two-line 16 character LCD (Liquid Crystal Display)
- 20 button keypad (built-in terminal)
- 24 hour clock/calendar, Y2k compliant
- Up to 22 sensor inputs; mass flow rate, temperature and 4-20 mA reference inputs
- Ability to group one or more inputs as a METER and to define a METER as the sum/difference of other METERS, up to a maximum of 16 METERS
- Up to eight 0-5 VDC or 4-20 mA outputs
- Mass flow computer redundancy using two Model 155`s for unsurpassed reliability
- Up to eight 5-amp alarm relays
- English or Metric units
- Multi-Point calibration factor for each METER
- User-entered METER I.D. number
- Automatic sensor out-of-tolerance indication, alarm and re-averaging for multi-point flow elements
- Easy input/output calibration--no pots
- Lagrangian polynomial calibration data interpolation for maximum accuracy
- User-selectable digital filtering
- Operating temperature range: -25 to 60°C
- Built-in flow totalizers and elapsed time
- Non-Incendive Approval (Ex nC IIC T4)
- Technician and user access codes
- Optional NEMA 4, NEMA 4X, NEMA 7 and 19" rack enclosures
- Identical software menus for all Models
- Built-in field calibrators
- Optional mass flow control of up to 4 separate In-Line Mass Flow Elements
- Configuration upload/download using IBM-compatible computers
- EMI Approvals; CE Compliance
- Optional "Flow Perfect"TM sensor array configuration correction factor
- Optional RS-232C data port on all models; RS-485 on selected models
- Choice of optically isolated loop-powered or self-powered 4-20 mA outputs
- Optional pulsed flow outputs for remote totalizers