The BMS-WiNG leverages RLE’s WiNG wireless sensor technology and allows it to integrate via protocols into any building management system (BMS) or alarm monitoring system.
Integrated Wireless Monitoring
Pair the BMS-WiNG with RLE’s WiNG wireless sensors to monitor a variety of conditions including temperature, humidity, dew point, and differential pressure, and integrate these sensor readings directly into a BMS or BAS.
What Sets The BMS-WiNG Apart?
- Designed specifically for system integration, the BMS-WiNG leverages robust protocol communications to communicate with any Modbus RTU or BACnet MS/TP system.
- A suite of sensors with an industry-leading 12 year battery life allow users to monitor conditions including temperature, humidity, dew point, & liquid leaks.
- Notifies users quickly when an alarm condition is met.
- Available in 900MHz and 868MHz configurations for domestic U.S. and international installations.
- No user interface or separate software required – integrates directly with existing BMS and alarm monitoring systems.
- Enclosure mounts in a panel, on a DIN rail, or on a wall.
- All the advantages found in our WiNG wireless sensors, including:
- Up to 12 year battery life
- Transmission range up to 600’ line of sight
- Packet transmission accuracy that exceeds 98%
- Supports up to 50 WiNG sensors
Power: Hardwired 24VDC, 500mA or RLE power supply PSWA-DC-24-ST (optional; not included)
Included Equipment: BMS-WiNG, DIN rail mount adapter, USB mini B to USB A cable
Required Accessories: WiNG sensors
Maximum Number of WiNG sensors per BMS-WiNG: 50 sensors
Communications: Available in 868MHz or 900MHz configurations
- EIA-232: USB Connector; 115200 Baud, 8 data bits, no parity, 1 stop bit
- EIA-485: 9600, 19200, 38400 or 76800 baud (selectable); Parity: None, 8 data bits 1 stop bit
Protocols
- Modbus RTU (EIA-485): Server RTU mode, supports function codes 03 and 04
- BACnet MS/TP (EIA-485)
External Interface
- Push Button: Sensor auto-discovery, sensor removal, and factory reset
- LED Indicators: Power/Status – 1 tricolor
- DIP Switches: SW 1 – Device configuration; SW 2 – Modbus/BACnet device ID
Operating Environment
- Temperature: 32°F to 122°F (0°C to 50°C)
- Humidity: 5% to 95% RH, non-condensing
Dimensions: 5.25”W x 6.0”H x 1.75”D (133mmW x 152mmH x 44.5mmD)
Weight: 8.0 oz. (228g)
Mounting: Wall mount (keyhole, zip tie, or screw holes); DIN rail mount
Certifications: CE; ETL listed: conforms to UL 61010-1, IEC 61010; EN 60601-1; CSA C22.2 NO. 61010-1; IEC 55011; CISPR16; RoHS compliant.